KP "Kolomyavoodokanal", Kolomya City, Ivano-Frankovskaya region
Kolomya City, Ivano-Frankovskaya region KP "Kolomyavoodokanal",
Sheparyvtsy settlement, Kolomyiskyi district.
Drinking water
December 2011
Before reconstruction
Water source - river Prut
Productive capacity - 15000 m3/24 hours
Maximum flow - 900 m3/hour
Pressure after water pump station - 2 and before clear-water reservoir - 1,8 bar
Dosage method - in the flow before clear-water reservoir
Chlorine residual at the city output - 1,2 mg/l
Water treatment method: disinfection by chlorine gas in balloons
TARGET
To resolve problems associated with chlorine circulation and storage. To select the most effective drinking-water disinfection technology.
SOLUTION
Mixed oxidants production system - MIOX RIO M2
System capacity - 54 kg equivalent to Cl2 per 24 hours.
Dosage method - in the flow before clear-water reservoir
Chlorine residual at the city output - reduced up to 0,8 mg/l
Dosage system - automatic.
Raw materials stock (salt) for mixed oxidants production - up to 5 months
Salt volume in salt dissolver - for 30 days
Mixed oxidants volume in storage tank- for 24 hours